Electrical Tools & Field Work

How to Calculate Wire Size, OCPD, and EGC for Motors

Learn how to calculate motor wire size, OCPD, and EGC with a simple motor circuit example and see how Sparky Toolbox speeds up the process.

Motor circuits use different steps for wire size, overcurrent protection, and the equipment grounding conductor.

A quick example makes it easier to see how the process works.

Quick Motor Circuit Example

Example: a 5 HP, 230V, single-phase motor using copper conductors, 75°C-rated terminals, and a time-delay fuse.

First, get the motor full-load current from NEC Table 430.248.

5 HP, 230V, single-phase motor = 28 amps

Step 1: Calculate the Minimum Wire Ampacity

For a single motor, use NEC 430.22 and size the branch-circuit conductors at 125% of the motor full-load current.

28 amps × 125% = 35 amps

The conductor needs an ampacity of at least 35 amps.

Using the 75°C column, #10 copper has a 35-amp ampacity, so #10 copper works for this example.

Step 2: Calculate the OCPD

For a time-delay fuse, use NEC Table 430.52.

28 amps × 175% = 49 amps

The next standard fuse size is 50 amps.

For this example:

OCPD = 50-amp time-delay fuse

Step 3: Size the EGC

Size the equipment grounding conductor from NEC Table 250.122 using the rating of the branch-circuit OCPD.

For a 50-amp OCPD:

EGC = #10 copper

Final Results for This Example

  • Motor full-load current: 28 amps
  • Minimum conductor ampacity: 35 amps
  • Wire size: #10 AWG copper
  • OCPD: 50A time-delay fuse
  • EGC: #10 AWG copper

How Sparky Toolbox Helps

Instead of looking up the motor current, calculating the conductor ampacity, checking the OCPD, and then finding the EGC size separately, enter the motor horsepower, voltage, phase, and protection type into Sparky Toolbox.

The Motor Calculator shows:

  • Recommended wire size
  • Fuse size
  • Breaker size
  • EGC size

That gives you a quick starting point when planning a motor circuit or building a material list.

Important Reminder

This is one simple example. Motor circuits can change based on terminal ratings, conductor type, motor duty, starting conditions, disconnects, overload protection, and other job details.

Always verify the current Code, equipment nameplate, manufacturer instructions, project requirements, approved plans, and local inspection requirements before installation.

Try Sparky Toolbox

Download the Sparky Toolbox app on our homepage